01
Check the DG room and surrounding area
Check the area before inspecting the generator.
- Keep access routes clear.
- Check ventilation openings and exhaust paths for obstructions.
- Look for spills, water accumulation, unsafe storage or visible hazards.
Record: Obstructions, spills, damage or unsafe conditions that need attention.
02
Check the engine oil level
Check the oil with the generator stopped, following the manufacturer's specified procedure and waiting period.
- Confirm the oil level is within the specified range.
- Look for visible oil leakage.
- Note unusual changes or signs of contamination.
Record: Oil level or indication, leakage and any abnormal change. Repeated oil loss needs investigation; topping up alone may not resolve the cause.
03
Check coolant and the cooling system
Check coolant only according to the manufacturer's safe procedure.
- Look for visible coolant leakage.
- Inspect accessible hoses and connections for damage.
- Note recurring low coolant or abnormal temperature indications.
Safety: Never open a hot, pressurized cooling system.
04
Inspect the battery and connections
The starting battery is essential for reliable DG operation, especially during automatic start demand.
- Look for visible damage, leakage or corrosion.
- Check accessible connections for visible looseness or damage.
- Check voltage if required by the approved procedure.
Record: Condition, voltage where checked and any warning. Voltage alone does not prove cranking capability.
05
Check the air cleaner indicator
Where a restriction indicator is fitted, check it according to the manufacturer's instructions.
- Note any restriction warning.
- Check accessible intake parts for visible damage or obstruction.
- Report a warning that requires filter inspection.
Record: Indicator status, visible damage and required follow-up.
06
Check fuel availability
Confirm that the available fuel is suitable for the site's required standby duration.
- Check the indicated or visible fuel level using the approved method.
- Look for visible leakage around accessible components.
- Note unusual changes or fuel-related concerns.
Record: Fuel indication and any abnormality. Do not assume one tank-fill percentage fits every installation.
07
Inspect accessible hoses, belts and connections
Look for visible signs of deterioration without touching hot or moving components.
- Cracks, wear or damage.
- Loose or visibly damaged connections.
- Oil, coolant or fuel seepage.
Record: Component, observed condition and any action needed.
08
Observe starting and engine operation
During an authorized start or test, observe the DG from a safe position. If an exhaust leak is suspected, keep personnel away, notify qualified maintenance personnel immediately, and follow the site safety procedure, including shutdown where required.
- Unusual cranking or starting behaviour.
- Abnormal noise, vibration, smoke or exhaust changes.
- Warning indicators or alarms.
Record: Symptom, alarm and when it occurred. A successful start does not mean every parameter is acceptable.
09
Check the controller and AMF panel
Inspect displayed status, alarms and operating mode where relevant.
- Record active warnings or fault codes.
- Note the displayed operating mode.
- Follow the approved procedure for functional automatic-operation tests.
A normal display alone does not prove the full mains-failure detection and transfer sequence works correctly. Testing must be authorized and protect connected loads.
10
Record applicable operating parameters
Where required and available, record actual values rather than writing only “OK.”
- Output voltage and frequency.
- Oil pressure and coolant temperature, if displayed.
- Load and running hours where applicable.
Record: Actual reading, unit and applicable OEM/site reference.
11
Observe for leaks and abnormal changes
From a safe position, look for fuel, oil or coolant leaks, new vibration, unusual sounds, smells, exhaust changes, warnings or readings outside applicable limits.
Record: Condition, time, relevant reading, person notified and action taken. Follow the site's escalation or shutdown procedure for unsafe conditions.
12
Document defects and follow-up
A useful record explains what was actually observed—not just “not OK.”
- Checklist item and component.
- Actual reading or evidence where relevant.
- Person notified, action owner and follow-up.
- Work-order reference and closure verification.
13
Complete the inspection record
Before closing the inspection, confirm that required checks are complete and that unresolved findings are visible to the next responsible person.
- Explain items marked defective, not applicable or unable to complete.
- Record actual readings required by the site procedure.
- Report outstanding issues and complete sign-off where required.
Record: Operator, date, time, outstanding actions and supervisor review where required.